Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T10CM00650
Inspection Description - FIRE - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/17/2010 | FIRE - FINAL | Approved | ||
| 06/04/2010 | FIRE - FINAL | Partial Approval | TEMP C OF O APPROVED - STILL NEED SPRINKER COVERAGE CORRECTED | |
| 06/01/2010 | FIRE - FINAL | Denied | 1. Correct sprinkler coverage by wall to sorting room sales floor, heads over 7' 6" away from wall. 2. Correct sprinkler coverage south/east wall sales floor no coverage, will need to add coverage. 3. Correct sprinkler coverage break room heads over 7' 6" away from wall. 4. Address numbers shall be posted on building per handout given. 5. Front doors do not match what is stated in approved plans front page states electric sliding doors to be added, 3 pages in states doors to have panic hardware installed. Doors on site are just push open type, will need to remove slide bolt locks from doors and use only approved type locks, will also need to change plans showing which door type that will be used. 6. Will need approved plans and permits for sprinkler work before work is started. |