Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T10CM00650
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/17/2010 | FIRE SPKLR - FINAL | Approved | ||
| 06/01/2010 | FIRE SPKLR - FINAL | Denied | 1. Correct sprinkler coverage by wall to sorting room sales floor, heads over 7' 6" away from wall. 2. Correct sprinkler coverage south/east wall sales floor no coverage, will need to add coverage. 3. Correct sprinkler coverage break room heads over 7' 6" away from wall. 4. Will need approved plans and permits for sprinkler work before work is started. |