Permit: T10CM00650

Parcel: 121060070


Addresses:

5665 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T10CM00650

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/24/2010 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
05/21/2010 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) FERNCO NOT ALLOWED INSIDE BLDG
2) TEST ON DWV OK
3) PROVIDE LISTED PIPE SUPPORTS ON OVERHEAD COPPER 6' MAX
4) OK TO COVER WALL
05/18/2010 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
INSTALL PER PLANS
EXPOSE TIE IN
PROVIDE A TEST
PROVIDE PROPER SUPPORTS