Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T10CM00646
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/30/2010 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
03/19/2010 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) A WATER HEATER SUPPORTED FROM THE GROUND SHALL REST ON LEVEL CONCRETE MIN 3" ABOVE GROUND UPC 508.3 2) PROTECTION FROM PHYSICAL DAMAGE IS REQUIRED FOR WATER HEATER INSTALLED IN CARPORT 3) CAP OR REMOVE HANDLES OF DRAIN VALVES ON COLLECTOR LOOP 4) PROPERLY INSTALL (PER MANUFACTURE INSTRUCTIONS) 5) INSULATION ON DOMESTIC PIPING-IE SEAL ALL JOINTS WITH ADHESIVE 6) PROTECT INSULATION AT STRUT CLAMPS 7) SECURE CLAMP ON EXP TANK 8) IDENTIFY WATER HEATER CIRCUIT BREAKER |