Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T10CM00621
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/27/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 11/30/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/27/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BLOCKING ON PVC PIPE NOT TO EXCEED 48" 2) BLOCK UP ELECTRICAL CONDUIT OFF OF ROOF 3) UNIT DATA PLATE NOT IDENTIFIED 4) PROVIDE SUN SHILED OVER FLEX CONNECTORS ON 3 SIDES 5) PROVIDE SERVICE OUTLET WITHIN 25' OF UNIT AT SAME LEVEL 6) PROVIDE CORRECT WIRE SIZE AT SERVICE TO UNIT 7) DO NOT USE WHITE WIRE AS HOT LEG 8) PROVIDE MINIMUM R-8 INSULATION AT ALL DUCT ON EXTERIOR OF BLDG AND WITHIN VENTED ATTIC 9) UNIT NOT LEVEL |
|
| 08/09/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
| 06/24/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/23/2010 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 05/06/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) UNIT NOT FUSED 2) PAINT CONDENSATE LINE 3) INSTALL REGISTERS |