Inspection History Details
Inspection Status: Not Applicable
Inspection History: ELECTRIC - PROGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/14/2010 | ELECTRIC - PROGRESS | Not Applicable | ||
| 06/18/2010 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) TERM BLOCK IS A RECOGNIZED COMPONENT-NOT FULLY LISTED AS STAND ALONE 2) 4 SQ BLANK CANNOT E USE AT ? NIPPLE AND NEED BONDING 250.92 |
|
| 05/27/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) ITEMS ON LIST OK 2) CALL BACK FOR FINAL |
|
| 05/17/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) REMOVE PAINT OR ENAMEL ON GROUNDING SURFACE OF METAL 250.12 NEC INSTALL NUT ON BOLT TO MAINTAIN TIGHT CONNECTION TO STEEL |
|
| 04/30/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) BE SURE STEEL STRUCTURE IS GROUNDED PER 250.32 NEC 2) OK U.G. & ROOF PV GROUNDING |
|