Inspection History Details
Inspection Status: Partial Approval
Inspection History: FRAMING
Permit Number - T10CM00611
Inspection Description - FRAMING
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/06/2010 | FRAMING | Partial Approval | IVRS - Inspection :* | |
07/06/2010 | FRAMING | Approved | IVRS - Inspection :* | |
06/07/2010 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NAIL PROTECT ELECTRICAL THROUGHOUT 2) GROUND METAL BOXES 3) MAKE UP SWITCHES PIGTAIL GROUNDS 4) PROVIDE ? PER CONNECTORS ROMEX TO BOX THROUGHOUT 5) INSTALL ANTI SCALD DIVERTER 6) NAIL PROTECT PLUMBING 7) TERMINATE HOMERUNS IN APPROVED BOX 8) OMIT ALL UNUSED WIRING 9) SECURE ROMEX 8" FROM BOXES THROUGHOUT 10) INSTALL HARD WIRED SMOKE ALARMS PER COD |
|
05/25/2010 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) RECALL WITH INTERMEDIATES |