Permit: T10CM00604

Parcel: 124060850


Addresses:

1106 E 7TH ST


Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T10CM00604

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/09/2010 BUILDING - FINAL Approved IVRS - Inspection :*
07/02/2010 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) POST ADDRESS FACING E. 7TH
2) VACUUM BREAKERS REQUIRED ALL HOSE BIBS
3) BUBBLE COVER REQUIRED ON EXT. OUTLETS
4) ARC-FAULT PROTECTION REQUIRED IN BEDROOMS OR REVISE PLAN TO REFLECT AS BUILT
5) FLEX LINE NOT ALLOWED ON PTR LINE
6) SECURE WATER HEATER VENT WITH 3 SCREWS AT ALL JOINTS AND PROVIDE SEDIMENT TRAP ON GAS LINE