Permit: T10CM00587

Parcel: 133200110


Addresses:

6534 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
04/28/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
04/27/2011 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :* ITEMS ON LIST NOT COMPLETED FROM LAST INSPECTION
04/21/2011 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REPAIR BROKEN CONDUIT AT CONDENSOR AND BE SURE FITTINGS ARE TIGHT
2) LOW VOLTAGE WIRE AT CONDENSOR MUST BE IN A CONDUIT TO PROTECT FROM DAMAGE
3) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMA FLEX AT CONDENSOR
4) DISCONNECT AT CONDENSOR IS LOOSE
5) USE PURPLE PRIMER ON ALL PVC JOINTS PRIOR TO GLUE
6) PROVIDE AN OVERFLOW SENSOR ON SECONDARY CONDENSATE DRAIN
7) MARK UNIT DATA PLATE AND FUSE ACCORDINGLY