Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/09/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/07/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS OFFICE AREA 2) OK HARD LIDS OFFICE AREA |
|
| 05/04/2010 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MC CABLE TO BE CONNECTED TO RACEWAY TO OUTDOOR BELL BOX 2) TIGHTEN MC CABLE CLAMPS 3) STRAP MC CABLES WITHIN 12" OF ENTERING PANEL 4) STRAP EMT TO WITHIN 3' OF ENTERING PANEL 5) SEAL OPEN KNOCKOUTS 6) PROTECT CABLES THAT ARE WITHIN 1 1/4" TO FACE OF STUD |