Permit: T10CM00574

Parcel: 12901027C


Addresses:

202 S TUCSON BL


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T10CM00574

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/16/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) TESTED DUCT SMOKE DETECTOR
2) OK FOR FINAL
12/15/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DUCT SMOKE DETECTOR NOT PROPERLY WIRED
12/13/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection
1) DUCT SMOKE DETECTOR NOT WIRED UP
2) THIS PROJECT IS BEING RE-FEED
12/10/2010 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) TECH TO BE ON SITE FOR TEST
12/09/2010 MECHANICAL - FINAL Cancelled CANCELLED PER PHILLIP ROSENBURG #975-5831
12/09/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ITEM 2 DATED 12/6/10 NOT CORRECTED ANY FURTHER INSPECTION DENIALS WILL RESULT IN A REFEE
12/06/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) NO AIR BALANCE REPORT ON SITE
2) DUCT SMOKE DETECTOR NOT INSTALLED IN CORRECT LOCATION. PROVIDE INSTALL LOCATION PER MANUFACTURERS INSTRUCTIONS
11/12/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE A DUCT SMOKE DETECTOR WITH AUDIBLE AND VISIBLE ALARM
2) PROVIDE CONDENSATE TRAP AS PER MANUFACTURERS INSTRUCTIONS
3) PROVIDE AIR BALANCE REPORT FOR OUTSIDE AIR
4) ALL CONDENSATE PIPE TO BE COPPER PER PLANS
11/09/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
1) DOORS LOCKED AND NO ACCESS