Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T10CM00574
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/25/2010 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
10/21/2010 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE ENOUGH SCREWS IN TOP FLANGES TO SEAL DUCT, SEE ITEM 3 DATED 8/10/10 2) REMOVE SHEETROCK IN RESTROOM TO VERIFY CONDENSATE PIPE IS INSULATED AS NOTED ON 8/10/10 3) NOTE: THE ABOVE ITEMS WERE NOTED ON 8/10/10 FAILURE TO CORRECT THESE ITEMS BY NEXT INSPECTION WILL RESULT IN A REFEE |
|
08/10/2010 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DOVE TAIL COLLARS NOT ALLOWED PER PLANS/DETAILS 2) PROVIDE 1" NCUSTICAL DUCT LINER IN CANS PER DETAIL NOT 1/2" 3) SEAL ALL DUCT JOINTS PER SMACNA 4) DUCT HANGERS NOT TO EXCEED 48" PER PLANS 5) EXHAUST DUCT ABOVE RESTROOM OK TO COVER 6) CONDENSATE PIPING TO BE INSULATED PER PLANS, NEED TO VERIFY PRIOR TO CLOSING UP WALLS |