Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T10CM00565
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/12/2010 | ELECTRIC - ABOVE CEILING | Approved | ||
04/30/2010 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) MEETING WAS HELD WITH DIRECTOR, AND ASSIANTS ARCHITECTS, CONTRACTORS AND INSPECTORS TO DISCUSS LIGHTING AND PLAN NEEDED-CONTRACTOR AND ARCHITECT TO PROVIDE PLANS |
|
04/05/2010 | ELECTRIC - ABOVE CEILING | Cancelled | IVRS - RI canceled | |
04/05/2010 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
04/03/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
04/01/2010 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) NO MORE THAN 360 DEGREE IN CONDUIT RUNS 2) MISSING "P" RINGS 3) FILL UNUSED OPENINGS IN BOXES 4) TIGHTEN LOOSE FITTINGS 5) STRAPS TO BE EFFECTIVE 6) NO LIGHTING PLAN TO SHOW WHAT WAS EXISTING OR WHAT IS NEW |