Permit: T10CM00544

Parcel: 12218257A


Addresses:

3719 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
07/09/2010 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
05/10/2010 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) ALL P PAGES REQUIRE REVIEWER STAMP (FOUND APPROVAL PAGE)
2) ALL CHANGES TO THE PLAN TO BE REDLINED BEFORE INSPECTION
3) 3" CLEANOUT CUT IN OK-OK TO COVER
4) INTERCEPTOR FILLED OK
05/07/2010 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) CORRECTIONS MADE FROM OBSERVATIONAL REPORT, MADE OK WITH NOTED EXCEPTIONS: FILL G.I. TO LID, INSTALL 3" G.C.O. AS REQUIRED, REDLINE ALL CHANGES APPROVED PLAN BEFORE NEXT INSPECTION AND OK TO BACKFILL EXCEPT 3" CLEANOUT CONNECTION
04/27/2010 PLUMBING - ROUGH, SOIL Denied 1) MUST TEST INTERCEPTOR ALL THE WAY TO LID
2) INSTALL 2 EACH HAND-SINK AND 1 EACH FLOOR SINK (ON PLAN BUT NOT INSTALLED)
3) FULL SIZE CLEAN-OUTS NEEDED ON 3" AND 4" DRAINS PER (NOT ON PLANS, NEED REVISION)
4) INSTALL BACKWATER VALVE SHOWN ON PLAN
5) INSTALL SEWER VENT FROM BACKWATER VALVE OUTLET (NOT SHOWN ON PLANS)
6) REVISE OR REDLINE PLANS TO SHOW AS-BUILT CONDITION AT NORTH-EAST CORNER (GCO DELETED)
7) REVISE PLAN TO INCLUDE WHATEVER THE 3" TRAP IS SERVICING JUST EAST OF THE RESTROOMS.
8) TRACER WIRE REQUIRED ON ALL SEWER (MISSING FROM INTERCEPTOR TO HCS)
9) VERIFY MINIMUM 1/8" SLOPE ON ALL PIPE. SEVERAL AREAS ARE BACK-PITCHED OR FLAT.