Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T10CM00541
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/29/2010 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* 1) INTERLOCK EXHAUST FAN WITH A/C SUPPLY FAN AS PER PLANS, WILL CHECK ON FINAL 2) FOR FINAL PROVIDE A FRESH AIR INTAKE, TERMINATE CONDENSATE TO AN APPROVED LOCATION, SUPPORT GAS LINE ON ROOF AND REPAIR BROKEN ELECTRIC CONDUIT TO DISCONNECT |