Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/01/2010 | MECHANICAL - FINAL | Approved | ||
| 08/31/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) DUCT SMOKE DETECTORS NOT SHUTTING DOWN A/C FANS 2) EVERYTHING ELSE OK |
|
| 08/30/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PROVIDE CORRECT DRAINS AT EXHAUST FANS 2) EXTEND 2 MORE SEWER VENTS 3) DUCT SMOKE DETECTORS MSUT BE AHEAD OF FRESH AIR INTAKES, FILTERS AND NEED TO BE WEATHERPROOF-PROVIDE INSTALL INSTRUCTIONS 4) CAPTURE AND TEST FAILED AT SMALL HOOD 5) LARGE HOOD OK 6) HEAT SENSOR TEST OK 7) NEED TO TEST DUCT SMOKE DETECTORS 8) PROVIDE AUDIBLE AND VISIBLE ALARMS 9) AIR BALANCE OK |
|
| 08/26/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) SECURE CONDENSORS ON ROOF 2) REMOVE ALL DUCT TAPE USED OUTDOORS 3) PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX 4) PERMANENTLY ID EQUIPMENT 5) EXTEND SEWER VENTS 2' ABOVE AIR INTAKES 6) PROVIDE GASKETS AND DRIP PANS AT FANS ON ROOF 7) SEAL ALL DUCT WORK ON ROOF 8) PROVIDE VENT HOOD FOR DAY AND NIGHT |