Permit: T10CM00535

Parcel: 13101014G

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
05/18/2010 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
05/06/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) FLEX DUCT SYSTEM NOT INSTALLED PER DETAILS ON PLANS, EXCEEDS 8' DID NOT FOLLOW TAPE AND CLAMP DETAIL
2) SUPPLY DIFFUSERS NOT PER PLAN
3) 16" SUPPLY DUCT SMASHED AND KINKED
4) FOR FINAL PROVIDE FRESH AIR INTAKE, PAINT EXPOSED PVC, PERMANENTLY I.D. EQUIPMENT, AIR BALANCE REPORT
5) LEFT GAS CARD