Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/18/2010 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 05/06/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) FLEX DUCT SYSTEM NOT INSTALLED PER DETAILS ON PLANS, EXCEEDS 8' DID NOT FOLLOW TAPE AND CLAMP DETAIL 2) SUPPLY DIFFUSERS NOT PER PLAN 3) 16" SUPPLY DUCT SMASHED AND KINKED 4) FOR FINAL PROVIDE FRESH AIR INTAKE, PAINT EXPOSED PVC, PERMANENTLY I.D. EQUIPMENT, AIR BALANCE REPORT 5) LEFT GAS CARD |