Permit: T10CM00535

Parcel: 13101014G

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
04/23/2010 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
04/12/2010 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) P1-IN 105 WATER TEST TO EXISTING OK
2) P2-IN 106 WATER TEST THRU ROOF OK
3) SUPPORT IN WALL AND OVERHEAD VENT PIPING AT CORRECT INTERVALS, PROVIDE PER CAP C.I. AT OLD LOCATION IN RESTROOM 105
4) P3 IS WATER DISPENSOR ONLY CAP DRAINAGE OR REVISE PLAN TO SHOW DRAINAGE
04/09/2010 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1) PLASTIC MAY NOT BE TESTED WITH AIR
2) FENCES NOT APPROVED FOR USE IN BLDG
3) NH COUPLINGS NOT APPROVED FOR USE IN TRANSITION
4) COPPER WATER PIPING SPECIFIED
5) CLEANOUT TEE NOT LISTED FOR HORIZONTAL CONCEALED USE