Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/04/2010 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 04/28/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) CANNOT USE BONDING LOCK NUT AT CONCENTRICS 2) CANNOT STACK LUGS 3) BOND DISCONNECT ENCLOSURE 4) PREVENT OBJECTIONABLE CURRENT AT SERVICE 250.6 5) NEED REJECTION PINS 6) LINE SIDE BOND JUMPERS TO BE PER 250.102 7) TIGHTEN LUG TERMINATIONS 8) PLANS NOT REFLECTIVE OF WORK INSTALLED WHERE IS 2ND METER AND LOADS |