Permit: T10CM00532

Parcel: 13323193C


Addresses:

750 N KOLB RD


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T10CM00532

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/14/2010 PLUMBING - FINAL Approved IVRS - Inspection :*
09/09/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) COMPLETE CORRECTIONS ON ROOF; A WALL HYDRANT IS NOT TO BE USED AS A CONTROL VALVE AND AN ATMOSPHERIC VACUUM BREAKER MAY NOT HAVE VALVES DOWN STREAM
2) PROVIDE TEST REPORTS FOR SODA ASSEMBLY AT BAR AND FOR IRRIGATION
3) LOW HAZARD BACKFLOW PROTECTION REQUIRED ON ALL OTHER NON CARBONATED BEVERAGES
08/24/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) COMPLETE ALL PREVIOUSLY NOTED ITEMS
2) PROVIDE SAFE ACCESS TO ROOF
3) REPLACE BROKEN CLEANOUTS PLUGS AND MISSING FD COVERS
4) FS'S REQUIRE GRATES
5) INSTALL ALL EQUIPMENT SHOWN ON A1
6) PROVIDE CORRECT DRAINAGE PIPING ALL INDIRECT WASTE PIPING UPC SECTION 801.2, 801.2.3
7) PROVIDE ALL REQUIRED BACKFLOW DEVICES REQUIRED PER UPC 602.2 AND 603
8) CONTINUED DENIED INSPECTIONS MAY RESULT IN REFEE'S
07/29/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) CORRECT WYE ON 3 COMP SINK DRAINAGE
2) COMPLETE CORRECTIONS ON ROOF
3) SECURE AND SEAL FIXTURES IN CONTACT WITH WALL
4) INSTALL ALL BEV EQUIPMENT AND INDIRECT DRAINAGE GOING TO NEW RECEPTORS
5) INSTALL AND CERTIFY ALL INTERNAL BACKFLOW ASSEMBLIES
6) TEST EXISTING INTERNAL BACKFLOW ASSEMBLIES
7) PROVIDE STERILIZATION OF WATER SYSTEM