Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T10CM00532
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/14/2010 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
09/09/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) COMPLETE CORRECTIONS ON ROOF; A WALL HYDRANT IS NOT TO BE USED AS A CONTROL VALVE AND AN ATMOSPHERIC VACUUM BREAKER MAY NOT HAVE VALVES DOWN STREAM 2) PROVIDE TEST REPORTS FOR SODA ASSEMBLY AT BAR AND FOR IRRIGATION 3) LOW HAZARD BACKFLOW PROTECTION REQUIRED ON ALL OTHER NON CARBONATED BEVERAGES |
|
08/24/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) COMPLETE ALL PREVIOUSLY NOTED ITEMS 2) PROVIDE SAFE ACCESS TO ROOF 3) REPLACE BROKEN CLEANOUTS PLUGS AND MISSING FD COVERS 4) FS'S REQUIRE GRATES 5) INSTALL ALL EQUIPMENT SHOWN ON A1 6) PROVIDE CORRECT DRAINAGE PIPING ALL INDIRECT WASTE PIPING UPC SECTION 801.2, 801.2.3 7) PROVIDE ALL REQUIRED BACKFLOW DEVICES REQUIRED PER UPC 602.2 AND 603 8) CONTINUED DENIED INSPECTIONS MAY RESULT IN REFEE'S |
|
07/29/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CORRECT WYE ON 3 COMP SINK DRAINAGE 2) COMPLETE CORRECTIONS ON ROOF 3) SECURE AND SEAL FIXTURES IN CONTACT WITH WALL 4) INSTALL ALL BEV EQUIPMENT AND INDIRECT DRAINAGE GOING TO NEW RECEPTORS 5) INSTALL AND CERTIFY ALL INTERNAL BACKFLOW ASSEMBLIES 6) TEST EXISTING INTERNAL BACKFLOW ASSEMBLIES 7) PROVIDE STERILIZATION OF WATER SYSTEM |