Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T10CM00531
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/04/2010 | FIRE - FINAL | Approved | Approved 5/4/10 | |
04/27/2010 | FIRE - FINAL | Denied | Not approved 4/27/10 1.) Lable the door for the electrical panel room,"ELECTRICAL" 2.) The hood system is current on the 6 month inspection but the appliance line-up has been changed from the original. 3.) Must reinspect the hood for proper: a.) nozzel placement b.) nozzel distance c.) nozzel flow points 4.) The nozzel piping for hood must be secured in place. 5.) Panic hardware on the north exit door is hard to open |