Permit: T10CM00531

Parcel: 140122150


Addresses:

5005 S CAMPBELL AV


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T10CM00531

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/04/2010 FIRE - FINAL Approved Approved 5/4/10
04/27/2010 FIRE - FINAL Denied Not approved 4/27/10
1.) Lable the door for the electrical panel room,"ELECTRICAL"
2.) The hood system is current on the 6 month inspection but the appliance line-up has been changed from the original.
3.) Must reinspect the hood for proper:
a.) nozzel placement
b.) nozzel distance
c.) nozzel flow points
4.) The nozzel piping for hood must be secured in place.
5.) Panic hardware on the north exit door is hard to open