Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
03/23/2010 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
03/18/2010 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) SEAL CONDUITS PER 300.7 INSIDE
2) LABEL BREAKER AS TO DISCONNECT WHEN UNIT IS CONTROLLED 408.4
3) GROUNDED CONDUCTOR TO BE WHTIE ENTIRE LENGTH 200.6
4) MAINTAIN WORKING SPACE IN FRONT OF DISCONNECT 110.26