Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T10CM00516
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/10/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
05/04/2010 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* SOME OF THE ISSUES WITH THIS EXISTING SERVICE: 1) INDOOR RATED EQUIPMENT 110.3 NEC 2) DBL LUGGING 110.3 NEC 3) MORE THAN 6 DISCONNECTS 230 NEC 4) SERVICES INTERCONNECTED 5) LINE AND LOAD (SUPPLY CONDUCTORS IN SAME RACEWAY OR ENCLOSURES) 230.7 NEC 6) MECHANICAL AND PLUMBING IN DEDICATED WORK SPACE, 110.26 NEC 7) TO MANY CODE VIOLATIONS TO ALLOW TO REMAIN-UPGRADE SYSTEMS |
|
04/28/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) MET WITH ELECTRIC CONTRACTOR ON SITE TO DISCUSS NEW SERVICE INSTALL, NO APPROVED PLANS AT THIS TIME 2) BE ADVISED BEFORE INSTALL TO PROVIDE DEDICATED ELECTRICAL SPACE PER 110.26 NEC 3) GROUNDING ELECTRODE CONDUCTOR HAS BEEN REMOVED (VANDALIZED) AND SHOULD BE REPLACED ASAP |