Permit: T10CM00507

Parcel: 130190930


Addresses:

4333 E 31ST ST


Inspection Status: Approved

Inspection History: BUILDING - PROGRESS

Permit Number - T10CM00507

Inspection Description - BUILDING - PROGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
03/15/2010 BUILDING - PROGRESS Approved CHECK #1100 FOR $75.00
03/04/2010 BUILDING - PROGRESS Not ready for Inspection 1) HAVE LICENSED ELECTRICIAN EVALUATE AND CORNER WIRING AS NEEDED AND ADD OUTLETS IN BEDROOM, SMOKIES IN ALL BEDROOMS, GFI'S ON ALL KIT. COUNTER OUTLETS AND BATH OUTLETS AND PROVIDE WRITTEN REPORT ON LETTER HEAD STATING SAME
2) HAVE LICENSED PLUMBER CORRECT REVERSED HOT & COLD IN WEST SHOWER AND CERTIFY ROUGH PLUMBING FUNCTIONS, INCLUDING WASHER DRAIN
3) OPEN WALLS TO VERIFY TREATED BOTTOM PLATES AND ANCHOR BOLTS
4) REMOVE EAST CARPORT AND INSTALL H2.5'S ON PATIO RAFTER TO FACIA CONNECTION AND BEAM TO POST HARDWARE