Permit: T10CM00487

Parcel: 110070130


Addresses:

2736 N EASTGATE DR

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
11/01/2012 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
10/29/2012 ELECTRIC - INTERMEDIATE Not ready for Inspection CANCELLED BY SONIA
10/01/2012 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CABLES TO BE SECURED TO BOXES AND EXHAUST FAN
2) FINISH MAKE UP
3)
4) NEED BOX FOR SMOKE DETECTOR
5) BOXES OVER FILLED
6) SECURE ALL CABLES WITHIN 12" OF BOXES AND EXHAUST FAN
7) PLEASE VERIFY DERATING OF WIRES IN RACE WAY ACROSS ROOF
8) FINISH BATHROOM WALL
9) LOW VOLTAGE SPLICE TO BE ACCESSIBLE.
04/02/2012 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*