Permit: T10CM00482

Parcel: 110120970


Addresses:

2600 N WYATT DR


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T10CM00482

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
08/05/2010 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
07/28/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROVIDE INSTALL INSTRUCTIONS FOR SMOKE DAMPERS
2) OK TO SHEETROCK PLAY AREA, OK TILES IN ROOMS WITH NO NEW MECHANICAL
06/23/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE FACE 1133 & AP1PA OFFICE 1711
06/16/2010 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1 - NEW 8" DUCT TAPPED INTO WRONG SYSTEM
2 - STILL NOT HAVE PROPER ACCESS TO SERVICEABLE EQUPMENT
3 - DUCT NOT PROPERLY SUPPORTED
4 - WORK NOT COMPLETE - OTHER AREAS AS WELL
06/08/2010 MECHANICAL - ABOVE CEILING Partial Approval 1) PROVIDE PROPER ACCESS TO EQUIPMENT ABOVE HARD CEILING PER SECTION 306 I.M.C.
06/07/2010 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) PROVIDE PROPER ACCESS TO EQUIPMENT ABOVE CEILING
2) FLEX RUNS NOT TO SPECS OR DETAILS