Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T10CM00482
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/05/2010 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 07/28/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE INSTALL INSTRUCTIONS FOR SMOKE DAMPERS 2) OK TO SHEETROCK PLAY AREA, OK TILES IN ROOMS WITH NO NEW MECHANICAL |
|
| 06/23/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE FACE 1133 & AP1PA OFFICE 1711 |
|
| 06/16/2010 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1 - NEW 8" DUCT TAPPED INTO WRONG SYSTEM 2 - STILL NOT HAVE PROPER ACCESS TO SERVICEABLE EQUPMENT 3 - DUCT NOT PROPERLY SUPPORTED 4 - WORK NOT COMPLETE - OTHER AREAS AS WELL |
|
| 06/08/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | 1) PROVIDE PROPER ACCESS TO EQUIPMENT ABOVE HARD CEILING PER SECTION 306 I.M.C. | |
| 06/07/2010 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE PROPER ACCESS TO EQUIPMENT ABOVE CEILING 2) FLEX RUNS NOT TO SPECS OR DETAILS |