Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
03/02/2010 BUILDING - FINAL Approved IVRS - Inspection :*
02/25/2010 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) CLEAN UP SUB PANEL IN NEW ROOM
2) INSULATE NEUTRALS AND GRDS, BUSHINGS AT K.O.'S
3) FIND FEEDER SOURCE FOR THAT PANEL
4) WHAT IS 50/50 BREAKER FOR ? SHOULD BE REMOVED IT'S ON A #10 CU. WIRE
5) FEEDERS FROM METER STRANDS CUT
6) REMOVE DBL TAP AT SERVICE, PUT SMALL DISCONNECT ON IT'S OWN BREAKER