Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/02/2010 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 02/25/2010 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CLEAN UP SUB PANEL IN NEW ROOM 2) INSULATE NEUTRALS AND GRDS, BUSHINGS AT K.O.'S 3) FIND FEEDER SOURCE FOR THAT PANEL 4) WHAT IS 50/50 BREAKER FOR ? SHOULD BE REMOVED IT'S ON A #10 CU. WIRE 5) FEEDERS FROM METER STRANDS CUT 6) REMOVE DBL TAP AT SERVICE, PUT SMALL DISCONNECT ON IT'S OWN BREAKER |