Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T10CM00452
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/06/2010 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
08/05/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
08/04/2010 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
06/29/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
06/25/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) 1ST FLOOR FINISH VDV 300.11 AND A/C ACCESS 110.26-WILL CHECK AT FINAL |
|
06/24/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) SUPPORT CONDUI AS PER CODE 3' + 10' 2) SUPPORT VDV CABLING 725.24 & 725.3, 800.24 & 800.3 AND 300.11 3) SEAL UNUSED RACEWAYS 4) FILL UNUSED OPENINGS IN BOXES 5) PROPERLY SUPPORT OLD BOXES 6) NEW WALL IMPEDING A/C DISCONNECT 110.26, ALSO CABLE TRAY |
|
06/23/2010 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |