Permit: T10CM00452

Parcel: 11713061K

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
08/06/2010 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
08/05/2010 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
08/04/2010 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
06/29/2010 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
06/25/2010 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) 1ST FLOOR FINISH VDV 300.11 AND A/C ACCESS 110.26-WILL CHECK AT FINAL
06/24/2010 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) SUPPORT CONDUI AS PER CODE 3' + 10'
2) SUPPORT VDV CABLING 725.24 & 725.3, 800.24 & 800.3 AND 300.11
3) SEAL UNUSED RACEWAYS
4) FILL UNUSED OPENINGS IN BOXES
5) PROPERLY SUPPORT OLD BOXES
6) NEW WALL IMPEDING A/C DISCONNECT 110.26, ALSO CABLE TRAY
06/23/2010 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*