Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T10CM00452
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/06/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
08/04/2010 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) M/C SUPPORTS TO BE INDEPENDENT OF CEILING WIRES 300.11 2) SECURE VDV CABLING TO CABLE TRAY UPON EXITING AND SUPPORT AS PER 725.24,800.24 AND 300.11 3) M/C CABLES FOR FIXTURE OVER 6' TO BE SUPPORTED 12" + 6' 4) FILL UNUSED OPENINGS IN BOXES 5) SUPPORT CONDUITS WITHIN 3' OF BOXES |
|
07/20/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK CONDUITS AND BOXES IN NEW STUD WALLS 1. FINISH CUT-INS FOR SWITCHES |
|
05/24/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) PREVIOUS INSPECTION 1ST FLOOR ONLY 2) OK WEST WALL ROOM 113 |
|
05/19/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALL STUD FRAME |
|
05/18/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PROPERLY SUPPORT EMT CONDUITS 2. PROTECT VDV CONDUITS FROM SHARP METAL EDGES 3. TIGHTEN LOOSE FITTINGS SECTIONS 725.3 & 24, 800.5 +24 WILL APPLY FOR VDV CABLING |