Permit: T10CM00452

Parcel: 11713061K

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/06/2010 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/04/2010 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) M/C SUPPORTS TO BE INDEPENDENT OF CEILING WIRES 300.11
2) SECURE VDV CABLING TO CABLE TRAY UPON EXITING AND SUPPORT AS PER 725.24,800.24 AND 300.11
3) M/C CABLES FOR FIXTURE OVER 6' TO BE SUPPORTED 12" + 6'
4) FILL UNUSED OPENINGS IN BOXES
5) SUPPORT CONDUITS WITHIN 3' OF BOXES
07/20/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK CONDUITS AND BOXES IN NEW STUD WALLS

1. FINISH CUT-INS FOR SWITCHES
05/24/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PREVIOUS INSPECTION 1ST FLOOR ONLY
2) OK WEST WALL ROOM 113
05/19/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALL STUD FRAME
05/18/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROPERLY SUPPORT EMT CONDUITS
2. PROTECT VDV CONDUITS FROM SHARP METAL EDGES
3. TIGHTEN LOOSE FITTINGS

SECTIONS 725.3 & 24, 800.5 +24 WILL APPLY FOR VDV CABLING