Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T10CM00449
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/17/2010 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
06/07/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE CLEARANCE TO COMBUSTIBLES FROM B-VENT 2) OK FOR TILES |
|
06/04/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1 SEAL VENTED ATTIC (2 PLACES) OR PROVIDE R-8 INSULATION ON ALL DUCT ABOVE CEILING 2) COMPLETE INSTALLATION OF RETURN GRILLS 3) OK TO COVER DUCT ABOVE CEILING AROUND SUPPLY GRILLS 4) COMPLETE OUTSIDE AIR DUCT ABOVE CEILING |
|
05/18/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* PROVIDE OVERFLOW SENSORS ON EVAP COOLER AS PER SECTION 307.2.3 2006 IMC. HAVE YOUR ENGINEER SHOW HOW FURNACES WILL BE VENTED TO THE OUTDOORS. ORIGINAL VENT EXISTS WITH NO VENT CONNECTORS. FLUE APPEARS TO BE TOO SMALL FOR THIS MUCH BTU INPUT. SEE SECTION 504 2006 IFGC |