Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T10CM00449
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/22/2010 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
06/16/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1 - REMOVE OR PROTECT HOSE BIBS 2 - SVB AT FILTERED WATER SUPPLY VI MAY NOT BE SUBJECT TO BACK PRESSURE FROM OVER HEAD PIPING. NOTE 3.6 PLUMBING SPECS ASK FOR HAMMER ARRESTORS AT SOLENOID VALVES 3 - 2 LEAKS AT VAC PUMP WATER SUPPLYU 4 - SECURE PIPING AT AIR COMPRESSOR AND CONENCT PROPLERY 5 - CORRECT LABELS AT VAC INLETS AS NOTED ON 5/20 6 - CAP OR REMOVE ABANDONED ROOF PENETRATIONS 7 - PROTECT PLASTIC VENT TERMINATIONS BY COMPLETING LEAD FLASHING INSTALLATIONS |
|
06/14/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* |