Permit: T10CM00449

Parcel: 12710084B


Addresses:

6126 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T10CM00449

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/22/2010 PLUMBING - FINAL Approved IVRS - Inspection :*
06/16/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1 - REMOVE OR PROTECT HOSE BIBS
2 - SVB AT FILTERED WATER SUPPLY VI MAY NOT BE SUBJECT TO BACK PRESSURE FROM OVER HEAD PIPING. NOTE 3.6 PLUMBING SPECS ASK FOR HAMMER ARRESTORS AT SOLENOID VALVES
3 - 2 LEAKS AT VAC PUMP WATER SUPPLYU
4 - SECURE PIPING AT AIR COMPRESSOR AND CONENCT PROPLERY
5 - CORRECT LABELS AT VAC INLETS AS NOTED ON 5/20
6 - CAP OR REMOVE ABANDONED ROOF PENETRATIONS
7 - PROTECT PLASTIC VENT TERMINATIONS BY COMPLETING LEAD FLASHING INSTALLATIONS
06/14/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*