Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T10CM00442
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/10/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
08/16/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) ONLY AUTHORIZED PERSONAL TO HAVE ACCESS 2) DO NOT ENERGIZE FEEDERS PRIOR TO INSPECTORS APPROVAL-LOCK OUT TAG OUT SES & EQUIP AS NECESSARY |
|
08/12/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) GROUNDING ELECTICAL CONDUCTOR SPLICE MUST BE IRRIVERSIBLE TYPE PER 250.64 C |
|
08/10/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) NEUTRAL TO BE RUN TO SERVICE MAIN DISC. SW'S PER 250.24 C NEC 2) ALSO NOT SUITABLE FOR SERVICE EQUIPMENT UNLESS NEUTRAL KIT #HN64? INSTALLED PER MANUFACTURE-SEE INFO ON BACK OF DISC. SW. COVER 3) INSTALL R-PINS IN DISC. SWITCHES 4) LABEL DISC. SWITCHES 5) UFER-GROUNDING ELECTRODE CONDUCTOR SHOULD BE TERMINATED PER 250.24 A-1 OR IN GUTTER OR SEE E2.1 PLANS MAIN SERVICE DISCONNECT |