Permit: T10CM00442

Parcel: 10609043B

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T10CM00442

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/10/2010 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/16/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) ONLY AUTHORIZED PERSONAL TO HAVE ACCESS
2) DO NOT ENERGIZE FEEDERS PRIOR TO INSPECTORS APPROVAL-LOCK OUT TAG OUT SES & EQUIP AS NECESSARY
08/12/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) GROUNDING ELECTICAL CONDUCTOR SPLICE MUST BE IRRIVERSIBLE TYPE PER 250.64 C
08/10/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) NEUTRAL TO BE RUN TO SERVICE MAIN DISC. SW'S PER 250.24 C NEC
2) ALSO NOT SUITABLE FOR SERVICE EQUIPMENT UNLESS NEUTRAL KIT #HN64? INSTALLED PER MANUFACTURE-SEE INFO ON BACK OF DISC. SW. COVER
3) INSTALL R-PINS IN DISC. SWITCHES
4) LABEL DISC. SWITCHES
5) UFER-GROUNDING ELECTRODE CONDUCTOR SHOULD BE TERMINATED PER 250.24 A-1 OR IN GUTTER OR SEE E2.1 PLANS MAIN SERVICE DISCONNECT