Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/04/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/03/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) BOXES MORE THAN 1/4" 314.20 2) GROUNDED CONDUCTOR 208/120 TO BE WHITE 3) PROTECT CONDUCTORS FROM SHARP METAL EDGES ROOF: 1) SMALL UNIT A/C DISCONNECT CANNOT BE MOUNTED ON UNIT |