Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/04/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/27/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SUPPROT VDV CABLING 725.24, 800.24 AND 300.112 2) NEED SUPPORT WIRE FOR EXIT SIGNS 3) ALL DEVICES 8' AND DOWN NEED TO BE INSTALLED FOR TEMP POWER 4) BOND RACEWAY FROM TRANSFORMER 5) ISOLATE CONDUCTOR AS DISCUSSED FOR SERVICE FEEDER PER 408.3 6) HAVE ENGINEER PROVIDE LETTER FOR MAIN IN SES |
|