Permit: T10CM00440

Parcel: 14026045A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T10CM00440

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/04/2010 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/27/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) SUPPROT VDV CABLING 725.24, 800.24 AND 300.112
2) NEED SUPPORT WIRE FOR EXIT SIGNS
3) ALL DEVICES 8' AND DOWN NEED TO BE INSTALLED FOR TEMP POWER
4) BOND RACEWAY FROM TRANSFORMER
5) ISOLATE CONDUCTOR AS DISCUSSED FOR SERVICE FEEDER PER 408.3
6) HAVE ENGINEER PROVIDE LETTER FOR MAIN IN SES
04/15/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) TIGHTEN LOOSE FITTINGS
2) PROTECT VDV CABLING FROM SHARP METAL EDGES
3) SUPPORT M/C WITHIN 12" OF BOXES AND FITTINGS
4) USE APPROVED SECUREING METHODS
5) OK WALLS AFTER CORRECTIONS