Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/06/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/18/2010 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SERVICE RACEWAY TO BE PROPERLY BONDED 2) INSTALL MAIN BONDING JUMPER IN SERVICE PANEL 3) MARK "SERVICE DISCONNECT" 4) COULD NOT VERIFY GROUNDING ELECTRODE SYSTEM AT SERVICE OR BLDG 5) BOND METAL WATER PIPE TO PANEL AT BLDG 6) ALL NEW WORK AT BLDG COVERED WITHOUT INSPECTIONS 7) NEED PROPER WORKING CLEARANCES IN FRONT OF PANELS 8) SECURE RECEPT AT PANEL TO BLDG 9) HAVE ELECTRICAL CONTRACTOR ON SITE FOR NEXT INSPECTION TO OPEN DEVICES AND PANELS |