Permit: T10CM00406

Parcel: 133382550

Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
05/15/2010 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
05/06/2010 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection :*
04/13/2010 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection :*
1) PROPERTY PINS REQUIRED, YOU CAN'T JUST DRIVE A STAKE IN THE GROUND AND CALL IT PROPERTY LINE. COULDN'T PULL OFF STRING ANYWAY TREES AND CACTUS IN THE WAY, YOU HAVE A TOLERANCE OF 2"
2) USE APPROVED CLAMP CU. NOT TO TOUCH STEEL DISIMILAR METALS, CLAMP IS NOT INSTALLED CORRECTLY AS IS
04/08/2010 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection :*
1) PLEASE I.D. PROPERTY LINE, I CANNOT ASSUME FENCES ARE PROPERTY LINES
2) OUT BLDG REQUIRES IT'S OWN GRD. SYSTEM, I SUGGEST A UFER GROUND