Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/24/2010 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 05/10/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1 ITEM 1 DATED 4/30/10 OK |
|
| 04/30/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE PROPER FLEX AT MED. PRESS. VAV INLETS 2) ALL OTHER DUCT ABOVE CEILINGS OK |
|
| 04/21/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE 2" BEADED COLLARS PER MANUFACTURERS INSTALLATION INSTRUCTIONS ON ALL FLEX CONNECTIONS 2) PROVIDE SEISMIC RESTRAINTS ON ALL REGISTERED AND GRILLS IN SUSPENDED CEILINGS |
|
| 04/14/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PHASE 2 ROUGH DUCT OK, OK TO INSULATE |
|
| 04/08/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) SUPPLY AND EXHAUST DUCTS ABOVE RESTROOMS OK TO COVER |
|
| 04/07/2010 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 04/06/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* COMPLETE SUPPLY AND EXHAUST ABOVE RESTROM/SHOWER AREA |
|
| 03/22/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* PROVIDE SMACMA STANDARD ON DUCT SUPPORT |