Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
05/24/2010 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
05/10/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1 ITEM 1 DATED 4/30/10 OK
04/30/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROVIDE PROPER FLEX AT MED. PRESS. VAV INLETS
2) ALL OTHER DUCT ABOVE CEILINGS OK
04/21/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROVIDE 2" BEADED COLLARS PER MANUFACTURERS INSTALLATION INSTRUCTIONS ON ALL FLEX CONNECTIONS
2) PROVIDE SEISMIC RESTRAINTS ON ALL REGISTERED AND GRILLS IN SUSPENDED CEILINGS
04/14/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PHASE 2 ROUGH DUCT OK, OK TO INSULATE
04/08/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) SUPPLY AND EXHAUST DUCTS ABOVE RESTROOMS OK TO COVER
04/07/2010 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
04/06/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
COMPLETE SUPPLY AND EXHAUST ABOVE RESTROM/SHOWER AREA
03/22/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
PROVIDE SMACMA STANDARD ON DUCT SUPPORT