Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/25/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK ELECTRIC |
|
| 05/24/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) SECURE POWER POLES AT TOP 2) VDV IMPROPERLY SUPPORTED 300.11, 725.24 AND 800.24 3) SECURE CABLE ? EXITING CABLE TRAYS 392.6 4) RECEIVED REQUESTED PAPERWORK |
|
| 05/21/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 05/20/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK FLAG POLE WIRING |
|
| 05/17/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 05/12/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) EXISTING LIGHTS IN ROOM DUE TO SAFETY CONCERNS WERE NOT INSTALLED PER CODES 2) GENERATOR LABELING NEEDED 700.8 3) NEED ONE CONDUCTOR PER LUG TERMINATION 4) BOXES MORE THAN 1/4" 314.20 |