Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/22/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/16/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEE ATTACHED INFO FOR WATER HEATER 422.13, 240 AND 310.16 NEC 2) WHAT IS THE 3/4" CONDUIT AND WIRE FOR AT THE BOTTOM OF PANEL ? NOT PART OF THIS PERMIT |
|
| 03/12/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL BOND BUSHING AT DISC. SW NEXT TO INVERTER AT NIPPLE WHERE USSING RE-WASHERS ALSO AT SERVICE LOCTAIONS 2) INSTALL CAUTION LABEL AT SERICE PANEL AND ID BREAKERS 3) GROUND WATER HTR. AT EQUIP. GROUNDING SCREW PROVIDED BY MANUF. CONDUCTOR SIZE FOR WATER HEATER IS #10 MIN PER 310.16 AND 240, 4D NEC |