Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T10CM00388

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/05/2010 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
03/03/2010 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REMOVE SHEETROCK TO EXPOSE CONDENSATE DRAIN IN WALL
2) USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE
3) PROVIDE 1/8" PER FT. SLOPE AND SUPPORT EVERY 4'
4) SEAL ALL ESSES AND DRIVES
5) PROVIDE BACKING AT SIDEWALL REGISTER BOXES
6) DO NOT USE PVC IN A RETURN AIR PLENIUM
7) PROVIDE A PLASTER GROUND FRAME FOR THE RETURN AIR GRILL