Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T10CM00388
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/05/2010 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
03/03/2010 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REMOVE SHEETROCK TO EXPOSE CONDENSATE DRAIN IN WALL 2) USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE 3) PROVIDE 1/8" PER FT. SLOPE AND SUPPORT EVERY 4' 4) SEAL ALL ESSES AND DRIVES 5) PROVIDE BACKING AT SIDEWALL REGISTER BOXES 6) DO NOT USE PVC IN A RETURN AIR PLENIUM 7) PROVIDE A PLASTER GROUND FRAME FOR THE RETURN AIR GRILL |