Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/25/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 04/22/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE A SECONDARY OVERFLOW SENSOR 2) PROVIDE A SEDIMENT TRAP ON GAS LINE 3) DO NOT USE WHITE WIRE FOR POWER TO CONDENSOR, TAPE BOTH ENDS BLACK 4) PROVIDE THE REQUIRED GFI SERVICE RECEPT ON ROOF 5) SUPPORT COPPER DRAIN LINE ON THE ROOF EVERY 6' AND SEAL SCREW HOLES |