Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit: T10CM00365

Parcel: 110113610


Addresses:

2490 N SWAN RD

Inspection Status: Approved

Inspection History: PLUMBING - ROOF DRAINS

Date Description Inspector Results Comments
11/24/2010 PLUMBING - ROOF DRAINS Approved IVRS - Inspection :*
11/23/2010 PLUMBING - ROOF DRAINS Not ready for Inspection IVRS - Inspection :*
1) PROVIDE SUPPORT AT 4' INTERVALS FOR HORIZONTAL PLASTIC PIPING
2) PROVIDE TEST ON RAIN DRAINAGE
3) VERIFY 4" X 6" SCUPPER OVERFLOW
11/19/2010 PLUMBING - ROOF DRAINS Not ready for Inspection IVRS - Inspection :*
1) COVERED WITHOUT INSPECTION
2) UN COVER ? AREAS OF ROOF DRAINS, PROVIDE TEST ON RAIN DRAINAGE