Permit: T10CM00365

Parcel: 110113610


Addresses:

2490 N SWAN RD


Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Permit Number - T10CM00365

Inspection Description - ELECTRIC - UFER

Inspection Status - Approved

Date Description Inspector Results Comments
12/08/2010 ELECTRIC - UFER Approved
11/16/2010 ELECTRIC - UFER Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) CONCRETE ENCASED REBAR ELECTRODE WAS AVAILABLE AND NOT USED
2) PLANS NOTE CONCRETE ENCASED ELECTRODE
3) 2 GROUND RODS AND #4 ARE PRESENT NEED ENGINEER APPROVAL FOR GROUNDING