Permit: T10CM00362

Parcel: 138043020


Addresses:

949 W CALLE ARAGON

Inspection Status: Approved

Inspection History: BUILDING - PROGRESS

Date Description Inspector Results Comments
03/04/2010 BUILDING - PROGRESS Approved IVRS - Inspection :*
02/18/2010 BUILDING - PROGRESS Denied IVRS - Inspection :
See detailed listing on site.| 999*
FRONT PORCH:
1) EXPOSE MINIMUM 1 FOOTER TO VERIFY DEPTH
2) EXPOSE MINIMUM 1 BASE CAP TO VERIFY
3) H2.5 CLIP RAFTER TO BEAM CONNECTIONS
4) INSTALL POST AT BEAM JOINT
BEDROOM ADDITIONS:
1) MISSING OUTLETS THROUGHOUT PER CODE
2) PROVIDE ACCESS TO ATTIC BEDROOM
3) EXPOSE BOTTOM PLATES TO VERIFY TREATED PLATES
4) EXPOSE ALL ELECTRICAL OR PROVIDE LETTERHEAD FROM LICENSED ELECTRICIAN STATING ALL WORK TO CODE AND VERIFY GROUNDING
5) MIXED 2 WIRE OUTLETS WITH 2 WIRE GROUND
OFFICE/DEN/LAUNDRY:
1) NOTES 1, 3 & 4 FROM BEDROOM
2) EXPOSE BEARING FOOTERS TO VERIFY DEPTH
3) LABEL ALL CIRCUITS PANEL
4) VERIFY AT LEAST ONE WINDOW EACH BEDROOM OPERATING FOR SAFE EGRESS