Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/24/2010 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 02/19/2010 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ELECTRIC: 1) OLD SERVICE LOCATION, TURNED INTO SUB PANEL AT THIS POINT, A 2ND FEEDER WAS INSTALLED FOR SUB PANEL IN NEW ADDITION NEW SUB PANEL NEEDS TO BE FED BACK TO SERVE PANEL (DBL TAPPED AT SUB) 2) AT NEW SUB 2 POLE 40 AMP BREAKER PROTECTING A #10 CU WIRE, USE SAME BREAKER AS PANEL TYPE 3) VERIFY GROUND AND H20 BOND AT SERVICE 4) NOTE: FURNACE ROOM/MISSING COMB/RELIEF DUCTS AND T & P LINE TO EXTERIOR |