Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/29/2010 | FRAMING | Approved | IVRS - Inspection :* | |
| 04/22/2010 | FRAMING | Not ready for Inspection | IVRS - Inspection :* | |
| 04/20/2010 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SECURE HOME RUNS 12" FROM SERVICE PANEL 2) MAKE UP ELECTRIC BOXES IN EXISTING HOUSE SECURE WIRES 12" FROM BOXES 3) PEX WATER LINES SHALL BE 12" FROM LIGHT CANS 4) PROTECT ABS PIPE CLOSER THAN 1 1/4" TO FACE OF STUD 5) DUCT SHALL BE R-8 INSULATION VALUE 6) CONNECT LAUNDRY FAN EXHAUST 7) GROUND ALL METAL BOXES 8) PROVIDE POSITIVE FLOW ON PTR LINE AT WATER HEATER 9) USE CPVC, COPPER OR IRON PIPE 10) WATER TEST REQUIRED ON NEW TUBS IN EXISTING HOUSE |