Permit: T10CM00300

Parcel: 10821018Y

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T10CM00300

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/06/2010 MECHANICAL - FINAL Approved
07/02/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) DUCT SMOKE DETECTOR FOR A/C NOT SETTING OFF AUDIBLE AND VISIBLE ALARM
2) EVERYTHING ELSE IS OK
07/01/2010 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
06/23/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE A BUSHING WHERE ELECTRIC CONDUIT PASSES THRU FAN CURB
2) SEAL ROOF JACK AT LAVE VOLTAGE CONDUIT
3) PERMANENTLY I.D. A/C UNITS
4) NEED TO TEST DUCT SMOKE DETECTORS
5) PROVIDE AUDIBLE AND VISIBLE ALARMS
6) AIR BALANCE REPORT OK