Permit: T10CM00300

Parcel: 10821018Y

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
06/09/2010 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
1) OK TO COVER DUCT ABOVE CEILING
06/07/2010 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) PHONED CONTRACTOR, NO ANSWER 3:10 PM ON 6/4/10
06/02/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) RAFTER TO SPECS AND DETAILS ON FLEX HANGERS, PROVIDE SHEETMETAL PER SMACNA
2) HANGERS NOT TO EXCEED 5'
3) PROVIDE SADDLES PER DETAILS
4) PROVIDE FULL 1 X RADIUS ON ALL FLEX BENDS PER SMACNA
5) PLUMBING TAPE IS NOT APPROVED AT A HANGER STRAP
6) INSULATE ALL DUCT EXCEPT EXHAUST