Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T10CM00300
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/09/2010 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* 1) OK TO COVER DUCT ABOVE CEILING |
|
06/07/2010 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) PHONED CONTRACTOR, NO ANSWER 3:10 PM ON 6/4/10 |
|
06/02/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) RAFTER TO SPECS AND DETAILS ON FLEX HANGERS, PROVIDE SHEETMETAL PER SMACNA 2) HANGERS NOT TO EXCEED 5' 3) PROVIDE SADDLES PER DETAILS 4) PROVIDE FULL 1 X RADIUS ON ALL FLEX BENDS PER SMACNA 5) PLUMBING TAPE IS NOT APPROVED AT A HANGER STRAP 6) INSULATE ALL DUCT EXCEPT EXHAUST |