Inspection History: ELECTRIC - FINAL

Permit Number - T10CM00287

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/20/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/19/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TIGHTEN FITTINGS ON ROOF FOR SEAL TIGHT
2) INSTALL BONDING BUSHING ON 480V CIRCUITS THRU CONCENTRICS AT ROOF TOP UNITS
3) INSTALL PROTECTIVE BUSHING ON CONNECTORS FOR CONDUCTORS #4 OR LARGER