Permit: T10CM00270

Parcel: 126191560


Addresses:

4425 E MONTECITO ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/25/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
02/04/2010 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE A MINIMUM 24" WIDE CAT WALK TO FURNACE AND A 30" WIDE PLATFORM FOR SERVICE
2) PROVIDE SUPPORT ON GAS LINE TO FURNACE
3) INSULATE ALL BARE SHEET METAL DUCTING IN ATTIC INCLUDING EXISTING DUCT AND PLENIUM WHERE INSULATION HAS DETERIORATED AND FALLEN OFF
4) SEAL DUCT CONNECTION TO FURNACE AND PLENIUM
5) PROPERLY TERMINATE THE INSULATION AND VAPOR BARRIER ON FLEX DUCT
6) LEFT GAS CARD
02/03/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*