Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/25/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 02/04/2010 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE A MINIMUM 24" WIDE CAT WALK TO FURNACE AND A 30" WIDE PLATFORM FOR SERVICE 2) PROVIDE SUPPORT ON GAS LINE TO FURNACE 3) INSULATE ALL BARE SHEET METAL DUCTING IN ATTIC INCLUDING EXISTING DUCT AND PLENIUM WHERE INSULATION HAS DETERIORATED AND FALLEN OFF 4) SEAL DUCT CONNECTION TO FURNACE AND PLENIUM 5) PROPERLY TERMINATE THE INSULATION AND VAPOR BARRIER ON FLEX DUCT 6) LEFT GAS CARD |
|
| 02/03/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* |